Why CO₂

No SF₆ and no fluorine. Carbon dioxide, kept dense.

A century of switching media

Every generation of circuit breaker has been defined by what fills it.

  1. Early 1900sWater and oil

    The first high-voltage breakers quenched arcs in liquid. Oil did it well, and it burned.

  2. ThenCompressed air

    No fire risk, but bulky for the fault current it could clear.

  3. 1950sSF₆

    Compact and very effective. It became the standard for high voltage.

  4. NextDense CO₂

    Insulation from density, with no fluorine.

History from A. J. Cruz Feliciano, Z. Jin, L. Graber, Applied Sciences 15(18), 2025.

Against SF₆

Global warming potential over 100 years, with areas drawn to scale. The CO₂ dot is inside the ring. IPCC Sixth Assessment Report.

Most high-voltage switchgear is insulated with sulfur hexafluoride. It works very well, and a leak stays in the atmosphere for roughly a thousand years.

What CO₂ brings

  • No fluorine

    Several SF₆ replacements are still fluorinated gases. CO₂ contains no fluorine.

  • Does not burn

    CO₂ is non-flammable. It is used to put fires out.

  • Available anywhere

    A common industrial gas, sold worldwide.

  • Familiar under pressure

    Refrigeration, fire suppression and food processing have run high-pressure CO₂ for decades.

Regulation

Europe's F-gas regulation restricts every fluorinated gas in new switchgear, SF₆ and its fluorinated replacements alike.

Switchgear voltageNot allowed in new equipmentFrom
Up to 24 kVAny fluorinated gas2026
24 to 52 kVAny fluorinated gas2030
52 to 145 kV, up to 50 kAFluorinated gases with a warming potential of 1 or more2028
Above 145 kV, or above 50 kAFluorinated gases with a warming potential of 1 or more2032

Fluorinated replacements for SF₆ are allowed only by exception, where no suitable fluorine-free option is offered. CO₂ is not a fluorinated gas, so these rules do not restrict it.

Regulation (EU) 2024/573, Article 13, simplified.

Built as pressure equipment

Our design target is about 100 bar, so every device will be a pressure vessel, built to pressure code with relief and controlled venting.

CO₂ is harmful to breathe at a few percent, so indoor installations get CO₂ monitoring and ventilation, as refrigeration plants do. In a hybrid breaker the switch opens without an arc, so there is little arcing to leave by-products.

Design pressures, relief arrangements and codes will be published with each device.