Why CO₂
No SF₆ and no fluorine. Carbon dioxide, kept dense.
A century of switching media
Every generation of circuit breaker has been defined by what fills it.
- Early 1900sWater and oil
The first high-voltage breakers quenched arcs in liquid. Oil did it well, and it burned.
- ThenCompressed air
No fire risk, but bulky for the fault current it could clear.
- 1950sSF₆
Compact and very effective. It became the standard for high voltage.
- NextDense CO₂
Insulation from density, with no fluorine.
History from A. J. Cruz Feliciano, Z. Jin, L. Graber, Applied Sciences 15(18), 2025.
Against SF₆
Global warming potential over 100 years, with areas drawn to scale. The CO₂ dot is inside the ring. IPCC Sixth Assessment Report.
Most high-voltage switchgear is insulated with sulfur hexafluoride. It works very well, and a leak stays in the atmosphere for roughly a thousand years.
What CO₂ brings
No fluorine
Several SF₆ replacements are still fluorinated gases. CO₂ contains no fluorine.
Does not burn
CO₂ is non-flammable. It is used to put fires out.
Available anywhere
A common industrial gas, sold worldwide.
Familiar under pressure
Refrigeration, fire suppression and food processing have run high-pressure CO₂ for decades.
Regulation
Europe's F-gas regulation restricts every fluorinated gas in new switchgear, SF₆ and its fluorinated replacements alike.
| Switchgear voltage | Not allowed in new equipment | From |
|---|---|---|
| Up to 24 kV | Any fluorinated gas | 2026 |
| 24 to 52 kV | Any fluorinated gas | 2030 |
| 52 to 145 kV, up to 50 kA | Fluorinated gases with a warming potential of 1 or more | 2028 |
| Above 145 kV, or above 50 kA | Fluorinated gases with a warming potential of 1 or more | 2032 |
Fluorinated replacements for SF₆ are allowed only by exception, where no suitable fluorine-free option is offered. CO₂ is not a fluorinated gas, so these rules do not restrict it.
Regulation (EU) 2024/573, Article 13, simplified.
Built as pressure equipment
Our design target is about 100 bar, so every device will be a pressure vessel, built to pressure code with relief and controlled venting.
CO₂ is harmful to breathe at a few percent, so indoor installations get CO₂ monitoring and ventilation, as refrigeration plants do. In a hybrid breaker the switch opens without an arc, so there is little arcing to leave by-products.
Design pressures, relief arrangements and codes will be published with each device.